Schneider Electric C25F47E160 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C25F47E160 ComPacT NSX 160A, 4P, MicroLog

MPNC25F47E160
Obsolete

Schneider Electric ComPacT NSX250F, C25F47E160, 160 A at 40 °C, 4P, MicroLogic 7.2 E electronic trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.

$1,784.39 – $4,477.14Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F47E160 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25F47E160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25F47E160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX250F
C25F47E160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25F47E160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25F47E160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

It carries a MicroLogic 7.2 E electronic trip unit rated at 160 A at 40 °C, with four poles (4P). The EN/IEC 60947-2 standard certifies it for industrial circuit-breaker duty, not just residential.

Protection and metering

The MicroLogic 7.2 E covers four protection functions: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage). That means one device handles both overcurrent and ground-fault protection — no separate RCD needed downstream. It also includes an energy meter with time-stamped histories, event tables, and demand current/power values, readable from the LCD display.

Mounts on a backplate in horizontal or vertical orientation, flat on the back. The 161 mm height, 140 mm width, and 86 mm depth fit standard distribution panel cutouts. Front connections on both upside and downside simplify bus-bar and cable routing. The toggle control and LCD display are accessible with the panel door closed if a cutout is provided.

Frequently asked questions

What is the breaking capacity of C25F47E160 at 415 V?

The breaking capacity is 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, which is the F breaking capacity code.

What protection functions does the MicroLogic 7.2 E trip unit provide?

It provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection.

What is the rated current of C25F47E160?

The rated current is 160 A at 40 °C.

How do I get current pricing and availability for C25F47E160?

The C25F47E160 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN