Skip to main content
Schneider Electric C25H32M220

Schneider Electric C25H32M220 ComPacT NSX250H, 220 A, 100 kA

MPN C25H32M220
Active

Schneider Electric ComPacT NSX NSX250H, 3P, 220 A, MicroLogic 2.2 M electronic trip unit, 100 kA Icu at 240 V AC, motor protection application.

$721.36 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25H32M220 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C25H32M220 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The Schneider Electric C25H32M220 is a ComPacT NSX250H moulded-case circuit breaker (MCCB) with a 220 A MicroLogic 2.2 M electronic trip unit, configured for motor protection across three poles. The H breaking capacity code delivers 100 kA Icu at 240 V AC and 70 kA at 415 V AC, both certified to IEC 60947-2 — sufficient for high-fault industrial distribution where the upstream transformer can deliver that level of prospective short-circuit current.

Trip unit and protection curves

The MicroLogic 2.2 M provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection, with motor tripping classes 5, 10, and 20 selectable. The 220 A rating at 65 °C means the breaker carries its full frame current without derating at that elevated ambient — critical for enclosed panels where internal temperature rise is a constraint.

Rated 100 kA Icu at 240 V AC, 70 kA at 415 V AC, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 690 V — all per IEC 60947-2. Under UL 60947-4-1 the ratings are 85 kA at 240 V, 65 kA at 480 V, and 15 kA at 600 V.

Physical integration and environment

Measures 161 x 105 x 86 mm (H x W x D), mounts on a backplate in horizontal or vertical orientation, and carries IP40 protection (IK07 impact resistance).

MPN
C25H32M220