Skip to main content
Schneider Electric C25H44V100

Schneider Electric C25H44V100 ComPacT NSX 100A 4P MCCB, 70 k

MPN C25H44V100
Active

Schneider Electric ComPacT NSX, NSX250H, 4P, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 70 kA Icu at 415 V AC, toggle control.

$1,407.81 – $3,245.40 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25H44V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C25H44V100 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

ComPacT NSX250H — 100 A, 4-pole MCCB with MicroLogic 4.2

The C25H44V100 is a Schneider Electric ComPacT NSX250H moulded-case circuit breaker in the ComPacT range, a 4-pole (4P) unit rated 100 A at 40 °C. It carries the MicroLogic 4.2 electronic trip unit, which integrates overload (L), short-time short-circuit (So), instantaneous short-circuit (I), and earth-leakage (R) protection in one package — no separate earth-leakage module needed. The local signalling — a flashing green LED for ready state, red at 105% Ir for overload, orange at 90% Ir — gives the panel tech a quick visual on load status without opening the door.

Breaking capacity and compliance

The breaking capacity curve is given at multiple voltage points per IEC 60947-2: 100 kA Icu at 220/240 V, 70 kA at 380/415 V, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V. For UL 60947-4-1 installations: 85 kA at 240 V, 65 kA at 480 V, and 15 kA at 600 V. IP40 front face, IK07 impact resistance — suited for enclosed panel mounting on a backplate (mounting support). The 35 mm connection pitch is standard for busbar systems.

MPN
C25H44V100