The MicroLogic 7.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — all adjustable through the front LCD interface. At 480 V AC the Icu is 65 kA under UL 60947-4-1, and at 690 V AC it drops to 10 kA — the curve matters if your fault current is high at the higher voltage.
Below that level it clears and is reusable; above it the breaker may need replacement. Electrical durability is 20,000 cycles at 440 V at half rated current (In/2), and 10,000 cycles at full 440 V In. For a distribution breaker that sees infrequent switching, this is well within normal service life; for a machine-tool disconnect that cycles daily, factor the electrical endurance.
The 35 mm connection pitch matches standard busbar systems. Front connections both top and bottom; neutral is on the left.