Skip to main content
Schneider Electric C25H47E250 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C25H47E250 ComPacT NSX250H, 250 A, 100 kA

MPNC25H47E250
Active

Schneider Electric ComPacT NSX, NSX250H, MCCB, 250 A, 100 kA Icu at 240 V AC, MicroLogic 7.2 E electronic trip unit, 4P, panel-mount.

$1,869.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25H47E250 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25H47E250 — Electrical Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25H47E250 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX250H
C25H47E250 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25H47E250 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25H47E250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25H47E250 is a Schneider Electric ComPacT NSX250H moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 250 A at 40 °C. Its breaking capacity hits 100 kA Icu at 240 V AC and 70 kA at 415 V AC per IEC 60947-2, which means it can safely interrupt fault currents up to those levels without upstream cascading — critical for high-fault installations like transformer secondaries or large motor control centres. The 4-pole design (4P) with toggle control and LCD display suits distribution boards where earth-leakage and overload protection must be coordinated. The MicroLogic 7.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — all adjustable via the front interface, so you can tune selectivity curves without swapping trip units.

The electronic trip unit draws power from the line side — no auxiliary supply needed.

Communication and data

The MicroLogic 7.2 E logs time-stamped event histories, maintenance indicators, instantaneous and demand values, power quality metrics, and energy metering. Five communication slots allow adding optional modules for remote monitoring via Modbus, Ethernet, or wireless — useful for condition-based maintenance or energy management in a plant.

Frequently asked questions

What is C25H47E250's breaking capacity at 415 V?

The C25H47E250 has a breaking capacity of 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the MicroLogic 7.2 E trip unit provide?

The MicroLogic 7.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection.

Where can I buy C25H47E250?

The C25H47E250 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C25H47E250