Skip to main content
Schneider Electric C25N47E250 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C25N47E250 ComPacT NSX250N, 250A, 50kA 41

MPNC25N47E250
Active

Schneider Electric ComPacT NSX, NSX250N, 250 A, 4P, MicroLogic 7.2 E electronic trip unit, 50 kA at 415 V AC.

$1,825.12 – $5,388.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25N47E250 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25N47E250 — Electrical Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25N47E250 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX250N
C25N47E250 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25N47E250 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25N47E250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C25N47E250 is a ComPacT NSX250N molded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 250 A at 40 °C.

The MicroLogic 7.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — all adjustable. The electronic trip unit logs time-stamped events, energy metering, and demand values, readable from the LCD display.

The C25N47E250's Icu varies by system voltage: 90 kA at 240 V AC, 50 kA at 380/415 V and 440 V, 36 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V AC. Under UL 60947-4-1 it's rated 85 kA at 240 V, 50 kA at 480 V, and 15 kA at 600 V AC. That's a wide coverage for mixed-voltage plants — a single breaker can serve a 480 V distribution board or a 600 V motor control center, but the 10 kA at 690 V means it's not a 690 V main.

Mounts on a backplate, flat on the back, in horizontal or vertical orientation. Five accessory slots for shunt trips, aux contacts, or communication modules.

Frequently asked questions

What are the key ratings for the C25N47E250?

250 A rated current at 40 °C, 50 kA Icu at 415 V AC, 4 poles, MicroLogic 7.2 E electronic trip unit with L, S, I, and R protection.

Where can I buy the C25N47E250?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What compliance standards does the C25N47E250 meet?

Designed to EN/IEC 60947-2 and UL 60947-4-1. Pollution degree 3 per IEC 60664-1. Operating altitude up to 2000 m without derating, 2000–5000 m with derating.

MPN
C25N47E250