Skip to main content
Schneider Electric C25V36E100 — Residual Current Breakers (RCCB/RCBO)

C25V36E100 ComPacT NSX 100A, MicroLogic 6.2 E, 85 kA

MPNC25V36E100
Active

Schneider Electric ComPacT NSX, 100 A, MicroLogic 6.2 E electronic trip unit, 85 kA Icu at 500 V AC, 3-pole, toggle control, LCD display, backplate mount.

$1,233.84Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V36E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25V36E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25V36E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250HB1
C25V36E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25V36E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25V36E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C25V36E100 is a ComPacT NSX moulded-case circuit breaker rated 100 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. The 6.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection — the G channel is the key differentiator from the 2.2 or 5.2 trip units, making this breaker suited for applications where ground-fault coordination is required, such as distribution panels feeding sensitive loads or sub-distribution in commercial buildings.

Breaking capacity and selectivity headroom

The HB1 breaking capacity code delivers 85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The 75 kA at 690 V is useful for 690 V distribution systems common in mining, marine, and heavy industrial installations.

Mounts on a backplate in horizontal or vertical orientation. IP40 enclosure protection and IK07 impact rating suit panel installation where occasional front-panel access is needed. The 35 mm connection pitch matches standard busbar and cable-lug spacing. Front-connect terminals on both line and load sides simplify busbar run and cable dressing within the enclosure.

Trip unit and metering capability

The MicroLogic 6.2 E includes an energy meter function and communicates instantaneous and demand values, demand current and power, maximeters/minimeters, power quality data, protection and alarm settings, energy metering, time-stamped histories, event tables, and maintenance indicators. The LCD display provides local readout of these values without needing a separate power meter.

Environmental and durability

Electrical durability is 20,000 cycles at 440 V at half-rated current, 10,000 cycles at full rated current, and 5,000 cycles at 690 V full current. Relative humidity range 0–95%.

Frequently asked questions

How do I get pricing and availability for C25V36E100?

Submit an RFQ through the storefront. The part is sourced to order through independent distribution; current pricing and availability are confirmed at quote time.

What is the breaking capacity of C25V36E100?

85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The HB1 code indicates a high-interrupting rating for this 100 A frame.

What protection functions does the MicroLogic 6.2 E trip unit provide?

It provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. The G channel enables ground-fault coordination, which the 2.2 and 5.2 trip units lack.

MPN
C25V36E100