Skip to main content
Schneider Electric C25V36E100

C25V36E100 ComPacT NSX 100A, MicroLogic 6.2 E, 85 kA

MPN C25V36E100
Active

Schneider Electric ComPacT NSX, 100 A, MicroLogic 6.2 E electronic trip unit, 85 kA Icu at 500 V AC, 3-pole, toggle control, LCD display, backplate mount.

$1,233.84 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25V36E100 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C25V36E100 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C25V36E100 is a ComPacT NSX moulded-case circuit breaker rated 100 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. The 6.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection — the G channel is the key differentiator from the 2.2 or 5.2 trip units, making this breaker suited for applications where ground-fault coordination is required, such as distribution panels feeding sensitive loads or sub-distribution in commercial buildings.

Breaking capacity and selectivity headroom

The HB1 breaking capacity code delivers 85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The 75 kA at 690 V is useful for 690 V distribution systems common in mining, marine, and heavy industrial installations.

Mounts on a backplate in horizontal or vertical orientation. IP40 enclosure protection and IK07 impact rating suit panel installation where occasional front-panel access is needed. The 35 mm connection pitch matches standard busbar and cable-lug spacing. Front-connect terminals on both line and load sides simplify busbar run and cable dressing within the enclosure.

Trip unit and metering capability

The MicroLogic 6.2 E includes an energy meter function and communicates instantaneous and demand values, demand current and power, maximeters/minimeters, power quality data, protection and alarm settings, energy metering, time-stamped histories, event tables, and maintenance indicators. The LCD display provides local readout of these values without needing a separate power meter.

Environmental and durability

Electrical durability is 20,000 cycles at 440 V at half-rated current, 10,000 cycles at full rated current, and 5,000 cycles at 690 V full current. Relative humidity range 0–95%.

MPN
C25V36E100