Skip to main content
Schneider Electric C25V36M220 — Residual Current Breakers (RCCB/RCBO)

Schneider C25V36M220 ComPacT NSX 220A MCCB, 85kA 500V, Micro

MPNC25V36M220
Active

Schneider Electric ComPacT NSX, MCCB, 220 A at 65 °C, 85 kA Icu at 500 V AC, MicroLogic 6.2 E-M trip unit, 3P, motor protection.

$1,034.02Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V36M220 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C25V36M220 — Electrical Ratings
ParameterValue
Rated current (In)220 A at 65 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25V36M220 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250HB1
C25V36M220 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25V36M220 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25V36M220 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25V36M220: Mounts on a backplate — standard for panel or enclosure mounting, not DIN rail. The 105 mm width, 161 mm height, and 86 mm depth fit the ComPacT NSX cutout; plan for front connections both top and bottom.

The LCD display shows energy metering data, thermal image, demand values, and event logs — useful for trending motor load without a separate power meter.

Frequently asked questions

What is C25V36M220's breaking capacity at 690 V?

75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2. The breaker code HB1 confirms the 75 kA rating at 690 V.

What motor tripping classes does the MicroLogic 6.2 E-M support?

Classes 5, 10, 20, and 30 are selectable. That covers fast-acting (class 5) through high-inertia loads (class 30).

MPN
C25V36M220