Skip to main content
Schneider Electric C25W36E100 — Residual Current Breakers (RCCB/RCBO)

C25W36E100 ComPacT NSX 100A 3P MicroLogic 6.2 E, 100 kA Icu

MPNC25W36E100
Active

Schneider Electric ComPacT NSX, 3P, 100 A at 40 °C, MicroLogic 6.2 E trip unit, 100 kA Icu at 690 V AC, EN/IEC 60947-2.

$1,039.71Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25W36E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25W36E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25W36E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250HB2
C25W36E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25W36E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25W36E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25W36E100 is a ComPacT NSX 3-pole circuit breaker carrying a MicroLogic 6.2 E electronic trip unit rated 100 A at 40 °C. The electronic trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, all adjustable via the LCD display. The 20-minute thermal memory before and after tripping prevents nuisance reclosing on a hot conductor — the breaker remembers the thermal state of the protected circuit even after a trip, so it won't re-energize until the conductor has cooled. Mounts on a backplate; IP40 and IK07 ratings suit panel-mount indoor use where occasional tool impact or dust ingress is possible.

Five accessory slots accept communication modules, auxiliary contacts, or shunt trips. The LCD display shows instantaneous and demand values, power quality, protection settings, time-stamped event logs, and energy metering — useful for commissioning verification without a separate meter.

Frequently asked questions

Where can I buy C25W36E100 and how do I get a price?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C25W36E100?

100 kA Icu at 500 V AC, 525 V AC, and 660/690 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the MicroLogic 6.2 E trip unit provide?

L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection.

MPN
C25W36E100