Skip to main content
Schneider Electric C25W36M220

Schneider C25W36M220 ComPacT NSX 220A MCCB, 100kA 690V

MPN C25W36M220
Active

Schneider Electric ComPacT NSX, NSX250HB2, MCCB, 3P, 220 A at 65 °C, 100 kA Icu at 690 V AC, MicroLogic 6.2 E-M electronic trip unit, motor protection.

$1,034.02 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25W36M220 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C

All specifications

C25W36M220 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The Schneider Electric C25W36M220 is a ComPacT NSX250HB2 moulded-case circuit breaker (MCCB) with a MicroLogic 6.2 E-M electronic trip unit, rated 220 A at 65 °C. It is built for motor protection in industrial distribution panels, carrying a 100 kA Icu breaking capacity at 690 V AC 50/60 Hz per IEC 60947-2. The 3-pole unit uses a toggle control and an LCD display for local metering and protection settings.

Motor tripping classes 5, 10, 20, and 30 are selectable, letting you match the trip curve to the motor's starting profile — class 10 for standard induction motors, class 20 or 30 for high-inertia loads like crushers or centrifuges. The 105 mm width and 161 mm height fit standard MCCB panel cutouts.

Deployment context

This MCCB is sized for motor feeder circuits in industrial control panels — typically feeding a motor starter or soft starter for pumps, conveyors, compressors, or fans. The electronic trip unit with ground-fault protection suits applications where earth-leakage detection is required without a separate relay. The LCD display provides real-time energy metering, demand current, and time-stamped event logs, useful for predictive maintenance without an external power meter.

Design complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. The enclosure carries IK07 impact protection per IEC 62262. Mechanical durability is rated at 20,000 cycles; electrical durability ranges from 5,000 cycles at 690 V In to 20,000 cycles at 440 V In/2.

MPN
C25W36M220