Schneider Electric C25W46E100 — Residual Current Breakers (RCCB/RCBO)

C25W46E100 ComPacT NSX 100A, 100kA Icu 690V AC MicroLogic 6.

MPNC25W46E100
Obsolete

Schneider Electric ComPacT NSX, NSX250HB2, 100 A at 40 °C, 100 kA Icu at 690 V AC, MicroLogic 6.2 E trip unit, 4 poles, toggle control, LCD display.

$16.21Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25W46E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25W46E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25W46E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250HB2
C25W46E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25W46E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25W46E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25W46E100 is a 4-pole ComPacT NSX moulded-case circuit breaker from Schneider Electric, fitted with a MicroLogic 6.2 E electronic trip unit rated 100 A at 40 °C. The E designation means it includes energy-metering functions — time-stamped event logs, demand current, power quality, and min/maximeters — alongside the standard L-S-I-G protection (long-time overload, short-time short-circuit, instantaneous, ground fault). That combination makes it a distribution breaker with built-in metering, not just a protection device. Breaking capacity is the headline: 100 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2, also 100 kA at 500 V and 525 V. The utilisation category is A (non-directional, no intentional delay to coordination), so it's a standard distribution breaker, not a selective main. Mechanical durability is 20,000 cycles; electrical durability varies by load — 20,000 cycles at 440 V In/2, 10,000 at 440 V In, 5,000 at 690 V In. That's typical for a 100 A frame in distribution duty; you wouldn't cycle it as a motor starter, but it's fine for infrequent switching or isolation.

Dimensions are 161 mm high, 140 mm wide, 86 mm deep — that's a compact footprint for a 100 A 4-pole breaker. Connection pitch is 35 mm, front-connected both upside and downside. Five slot positions are available for auxiliary contacts, shunt trips, or communication modules — the MicroLogic 6.2 E already occupies one slot internally, leaving four free for accessories. The LCD display shows protection settings, metering data, and alarm logs; local signalling includes a flashing green LED for ready, red LED at 105 % Ir for overload, and orange at 90 % Ir. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating. IK07 impact protection per IEC 62262 means it withstands a 2 J impact — enough for panel handling, not for exposed outdoor use.

Frequently asked questions

What is the breaking capacity of C25W46E100?

100 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2, also 100 kA at 500 V and 525 V. The breaking capacity code is HB2.

What protection functions does the MicroLogic 6.2 E trip unit provide?

L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault). Plus energy metering with time-stamped logs, demand current, power quality, and min/maximeters.

MPN
C25W46E100