Schneider Electric C25W46E160

Schneider Electric C25W46E160 ComPacT NSX, 160 A, 100 kA Icu

MPN C25W46E160
Active

Schneider Electric ComPacT NSX, NSX250HB2, C25W46E160, 160 A at 40 °C, 100 kA Icu at 690 V AC, MicroLogic 6.2 E trip unit, 4P, EN/IEC 60947-2.

$13.63 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25W46E160 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C

All specifications

C25W46E160 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

ComPacT NSX with MicroLogic 6.2 E — 160 A, 100 kA Icu

The Schneider Electric C25W46E160 is a ComPacT NSX molded-case circuit breaker rated 160 A at 40 °C, with a MicroLogic 6.2 E electronic trip unit providing L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground-fault) protection per EN/IEC 60947-2.

The 4-pole (4P) configuration with neutral on the left covers three-phase plus neutral distribution. Electrical durability is rated 20,000 cycles at 440 V at rated current (In), and 10,000 cycles at 440 V at In; mechanical durability is 20,000 cycles. This gives a realistic service life for frequent switching in distribution panels.

The front-connect terminals (upside and downside) simplify bus-bar or cable routing in a panel.