Schneider Electric C4047A400 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C4047A400 ComPacT NSX Trip Unit, MicroLog

MPNC4047A400
Active

Schneider Electric ComPacT NSX400...630, MicroLogic 7.3 E AL trip unit, 400 A at 40 °C, 4P, LSI protection, integrated earth leakage, LCD display, EN/IEC 60947-2.

$1,542.88 – $2,667.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C4047A400 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C4047A400 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
C4047A400 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C4047A400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C4047A400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Trip unit for ComPacT NSX — MicroLogic 7.3 E AL, 400 A, 4P

The Schneider Electric C4047A400 is a MicroLogic 7.3 E AL electronic trip unit for the ComPacT NSX400...630 range, rated 400 A at 40 °C in a 4-pole (4P) form factor. It provides LSI protection — long-time (L), short-time (S), and instantaneous (I) — plus integrated earth-leakage protection (Class A). The LCD display shows energy metering, protection settings, event logs, and demand values. Designed for distribution applications, it complies with EN/IEC 60947-2.

The long-time pickup (Ir) is adjustable from 160 to 400 A, so you can dial it down to match a smaller load without swapping the trip unit. Short-time protection (Isd) is also adjustable, with delay settings from 0 to 0.4 s (I²t on or off). Instantaneous pickup (Ii) is adjustable as well. The 4-pole configuration supports 3D + N/2, 4D, or 3D neutral protection modes. The integrated earth-leakage protection (Class A) can be switched off via the IΔn rotary switch.

This trip unit mounts into a fixed-mount ComPacT NSX400...630 circuit breaker (left-hand neutral position). The LCD display and LED indicators (green ready, red overload at 105% Ir, orange overload at 90% Ir) give local status without opening the panel door.

Frequently asked questions

How do I get current pricing and availability for C4047A400?

The C4047A400 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is C4047A400's listed range (ComPacT) on this component line?

The C4047A400 belongs to the ComPacT NSX400...630 range of electronic trip units.

What is C4047A400's listed standards (EN/IEC 60947-2) on this component line?

The C4047A400 complies with EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear assemblies.

What compliance documentation does this brand provide for C4047A400 (RoHS, REACH, UL, IEC)?

The C4047A400 is certified to EN/IEC 60947-2 and carries an IP40 rating per IEC 60529. The manufacturer provides standard compliance documentation; specific RoHS/REACH/UL declarations are available on request through the RFQ process.

MPN