Skip to main content
Schneider Electric C40F4 — Miniature Circuit Breakers (MCB)

C40F4 ComPacT NSX400F Basic Frame, 400 A, 36 kA at 415 V

MPNC40F4
Active

Schneider Electric ComPacT NSX400F basic frame, C40F4, 400 A at 40 °C, 36 kA Icu at 415 VAC, 4 poles, without trip unit, fixed mount.

$434.86 – $619.99Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C40F4 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeBasic frame
Device applicationDistribution
C40F4 — Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Poles configuration4P
Breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40F4 — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)15000 cycles conforming to IEC 60947-2
C40F4 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
C40F4 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
C40F4 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 UL 60947-4-1

Product details

What this frame is and what it needs

The C40F4 is a ComPacT NSX400F basic frame — a 4-pole, 400 A rated (at 40 °C) air circuit breaker chassis that ships without a trip unit. You add the protection module (Micrologic electronic or thermal-magnetic) separately to set the overload and short-circuit curves. This is the standard way Schneider sells the NSX line above 100 A: the frame and the trip unit are separate line items so you match the protection to the load without swapping the whole breaker. Breaking capacity varies by voltage: 85 kA at 240 V AC (UL 508), 36 kA Icu at 380/415 V AC (IEC 60947-2), and 25 kA Icu at 500 V AC. At 690 V AC it still holds 10 kA Icu, enough for most industrial line-to-line faults.

Because it is a frame without a trip unit, stocking patterns vary — distributors often carry the frame and the trip units separately. The frame itself is a single mechanical assembly; the buying decision is pairing it with the right Micrologic or TM-D trip unit for your load.

Fixed-mount design for backplate installation. Front-connected both top and bottom, so cabling is accessible without reaching behind the panel. IP40 front face protection keeps dust and tools out of the mechanism; IK07 impact rating means it shrugs off accidental knocks during installation. Overvoltage category III suits fixed-installation distribution boards.

Certified to EN/IEC 60947-2 (low-voltage switchgear and controlgear — circuit breakers) and UL 60947-4-1 (motor-protective circuit breakers). The dual listing covers both IEC and UL installations, so the same frame works in a European panel or a North American motor control center. Rated insulation voltage 800 V AC, rated impulse withstand 8 kV. The Class II insulation on the front face means no protective earth connection is required for the operator interface — the toggle and escutcheon are double-insulated.

Frequently asked questions

Where can I buy C40F4 and what is the lead time?

C40F4 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What trip unit does C40F4 need?

As a basic frame without protection, C40F4 requires a separately ordered trip unit — either a Micrologic electronic trip unit or a thermal-magnetic TM-D. The trip unit plugs into the frame's cradle and sets the overload and short-circuit protection curves.

What is the breaking capacity of C40F4 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 240 V AC it breaks 85 kA per UL 508, and at 690 V AC it still holds 10 kA Icu.

What compliance documentation does Schneider provide for C40F4?

The frame is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 and IK07 protection ratings, pollution degree 3 per IEC 60664-1, and overvoltage category III. The front face is Class II insulated.

MPN
C40F4