Skip to main content
Schneider Electric C40H44V400 — Residual Current Breakers (RCCB/RCBO)

Schneider C40H44V400 ComPacT NSX 400A MCCB, 100kA Icu

MPNC40H44V400
Active

Schneider Electric ComPacT NSX, MCCB, 400A, 4P, 100 kA Icu at 240 V AC, MicroLogic 4.3 trip unit, toggle control, backplate mount.

$5,960.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40H44V400 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40H44V400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40H44V400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX400H
C40H44V400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40H44V400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40H44V400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C40H44V400 is a ComPacT NSX400H molded case circuit breaker rated 400 A at 40 °C, 4-pole, with an integrated MicroLogic 4.3 electronic trip unit. Backplate-mounted, toggle-operated, front-connected.

The MicroLogic 4.3 trip unit combines L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection in one package. The earth-leakage is integrated, not a separate module — saves a slot in the panel.

Lifecycle status is current production. No end-of-life notification or successor order code is known.

IP40 enclosure rating (IK07 impact) suits clean indoor panel environments — not rated for washdown. Electrical durability: 12,000 cycles at 440 V at half-rated current, 6,000 cycles at full rated current. Mechanical durability: 15,000 cycles.

Frequently asked questions

What is the breaking capacity of C40H44V400 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 65 kA Icu; at 480 V UL rating it holds 65 kA Icu.

What protection functions does the MicroLogic 4.3 trip unit provide?

L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage protection). All four are integrated into the trip unit.

What compliance documentation is available for C40H44V400?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. Pollution degree 3 per IEC 60664-1. IP40 per IEC 60529, IK07 per IEC 62262.

MPN
C40H44V400