The Schneider Electric C40H44V400 is a ComPacT NSX400H molded case circuit breaker rated 400 A at 40 °C, 4-pole, with an integrated MicroLogic 4.3 electronic trip unit. Backplate-mounted, toggle-operated, front-connected.
The MicroLogic 4.3 trip unit combines L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection in one package. The earth-leakage is integrated, not a separate module — saves a slot in the panel.
Lifecycle status is current production. No end-of-life notification or successor order code is known.
IP40 enclosure rating (IK07 impact) suits clean indoor panel environments — not rated for washdown. Electrical durability: 12,000 cycles at 440 V at half-rated current, 6,000 cycles at full rated current. Mechanical durability: 15,000 cycles.