It carries a MicroLogic 4.3 electronic trip unit rated at 400 A at 40 °C, so the continuous current capacity is set for a 400 A bus or feeder — no need to oversize for ambient unless the panel exceeds 40 °C. The breaking capacity hits 50 kA Icu at 415 V AC (50/60 Hz), which is the N-frame rating; that means it can safely interrupt a fault up to 50 kA symmetrical at typical European 400 V distribution voltage without welding contacts or venting gas into adjacent gear. The earth-leakage protection is built into the trip unit, not a separate module — the R (residual) function is part of the MicroLogic 4.3's protection suite alongside L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit).
Mounts on a backplate in horizontal or vertical orientation. IP40 enclosure rating protects against tools and wires over 1 mm.
Protection logic and coordination
Category A utilisation means it is not intended for frequent switching of motor loads; this is a distribution breaker, not a motor-circuit protector.
Lifecycle stage is current — active catalogue item. Compliance per EN/IEC 60947-2 and UL 60947-4-1.