Skip to main content
Schneider Electric C40W46E400 — Residual Current Breakers (RCCB/RCBO)

C40W46E400 ComPacT NSX 400A, 100kA Icu 690V AC, MicroLogic 6

MPNC40W46E400
Active

Schneider Electric ComPacT NSX, NSX400HB2, 400 A, 100 kA Icu at 690 V AC, 4P, MicroLogic 6.3 E electronic trip unit, LCD display, toggle control.

$23.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40W46E400 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40W46E400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40W46E400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX400HB2
C40W46E400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40W46E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40W46E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C40W46E400 is a ComPacT NSX molded case circuit breaker (MCCB) rated 400 A at 40 °C, with a MicroLogic 6.3 E electronic trip unit providing L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground fault) protection. The 4-pole (4P) configuration with neutral on the left suits three-phase plus neutral distribution panels, and the 185 mm width and 255 mm height fit standard backplate mounting patterns.

Trip unit and metering capability

The LCD display and energy meter function give real-time demand current, power quality, and time-stamped event logs, which a panel builder can use for load profiling without adding a separate power monitor.

The IK07 impact rating (IEC 62262) handles accidental tool drops during commissioning.

Frequently asked questions

What is C40W46E400's breaking capacity?

100 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2, with the same rating at 500 V and 525 V AC.

What protection functions does the MicroLogic 6.3 E trip unit provide?

L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) — four protection curves in one electronic trip unit.

Where can I buy C40W46E400?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation is available for C40W46E400?

The breaker is certified to EN/IEC 60947-2, carries pollution degree 3 and overvoltage category III ratings, and is designed for distribution applications. Specific RoHS/REACH/UL declarations are provided with the shipment documentation.

MPN
C40W46E400