Skip to main content
Schneider Electric C60H1P25AB — 1-Pole MCB (DIN Rail)

Schneider C60H1P25AB MCB, 25A B-Curve, 1P, 15kA

MPNC60H1P25AB
Obsolete

Schneider Electric C60H1P25AB, Multi9 C60H series, miniature circuit breaker, 25 A, B-curve, 1-pole, 15 kA breaking capacity at 230 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P25AB — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P25AB — Electrical & Protection
ParameterValue
Rated current (In)25 A at 30 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P25AB — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H1P25AB — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P25AB — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

What this MCB does on the panel

The Schneider Electric C60H1P25AB is a 1-pole miniature circuit breaker from the Multi9 C60H range, rated 25 A at 30 °C with a B-curve magnetic trip threshold of 3 to 5 times In.

Breaking capacity and fault clearing

The C60H1P25AB carries a 15 kA Icu at 230…240 V AC (IEC 60947-2), which is the headline fault-clearing number for a 230 V distribution panel. At 400…415 V AC the Icu drops to 4 kA — still adequate for most sub-distribution boards but worth noting if the breaker sits on a 400 V bus. Rated impulse withstand voltage is 6 kV, covering typical transient overvoltages in industrial environments.

Integration into a distribution board

The toggle provides local ON/OFF indication and a contact position indicator confirms the state of the main contacts — useful during panel commissioning or fault finding when the breaker is locked out. The operating temperature range is -25 to 60 °C, storage -40 to 70 °C, with 95% relative humidity at 55 °C (tropicalisation class 2 per IEC 60068-1).

Frequently asked questions

Where can I buy C60H1P25AB and how do I get a price?

The C60H1P25AB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for C60H1P25AB?

Rated current 25 A at 30 °C, B-curve (magnetic trip 3-5 x In), 1-pole, breaking capacity 15 kA Icu at 230 V AC, rated operational voltage 440 V AC, insulation voltage 500 V AC.

What is C60H1P25AB's listed depth (73 mm) on this component line?

The C60H1P25AB has a depth of 73 mm, which is the standard depth for the C60H series 1-pole MCB on a DIN rail.

What compliance documentation does this brand provide for C60H1P25AB (RoHS, REACH, UL, IEC)?

The C60H1P25AB is designed to IEC 60947-2 for breaking capacity, insulation, and isolation suitability. Tropicalisation conforms to IEC 60068-1. Specific RoHS/REACH/UL declarations should be requested at quote time as they are not listed in the core spec record.

MPN