The Schneider Electric C60H1P2AC is a 2 A, 1-pole miniature circuit breaker from the Multi9 C60 series, with a C-curve trip characteristic (magnetic tripping at 5–10× In). The thermal-magnetic trip unit protects against overload and short-circuit, with a breaking capacity of 15 kA Icu at 230–240 V AC 50/60 Hz per IEC 60947-2 — enough for most commercial and light industrial panelboards.
The 2 A rated current (at 30 °C) sets the continuous load limit for the protected circuit — sized for lighting or control circuits drawing under 2 A, not motor or power feeders. The C-curve (5–10× In) means the magnetic trip holds through moderate inrush, so it suits transformer or capacitive loads that see a short current spike on energization. The 1-pole construction protects a single phase or line conductor.
The 18 mm width (2 modules) fits standard distribution board cutouts. Wire stripping length is 14 mm. The toggle switch provides local ON/OFF indication and a contact position indicator confirms the state of the contacts.