Skip to main content
Schneider Electric C60H1P2AD — 1-Pole MCB (DIN Rail)

Schneider C60H1P2AD MCB, D Curve 2 A, 1P, 15 kA

MPNC60H1P2AD
Obsolete

Schneider Electric, Multi9 range, C60H1P2AD, miniature circuit breaker, D curve, 2 A, 1P, 15 kA at 230 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P2AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P2AD — Electrical & Protection
ParameterValue
Rated current (In)2 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P2AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H1P2AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P2AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The Schneider Electric C60H1P2AD is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 2 A with a D tripping curve. The thermal-magnetic trip unit handles the overload side; the magnetic element handles short-circuit.

Breaking capacity and service continuity

Rated Icu of 15 kA at 230...240 V AC and 4 kA at 400...415 V AC, both per IEC 60947-2. At 60 V DC the Icu is 20 kA (1P), and at 130 V AC it reaches 30 kA. The limitation class is 3, so it lets through less fault energy than a standard Class 2 breaker, reducing stress on downstream components.

Snaps onto 35 mm symmetrical DIN rail, occupies 2 modules (18 mm per pitch). Depth is 73 mm, height 81 mm. Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, with 95 % relative humidity at 55 °C. Tropicalisation per IEC 60068-1 is included — the breaker is treated for warm, humid environments without condensation inside the enclosure. Operating altitude is rated to 2000 m.

Frequently asked questions

What is C60H1P2AD's breaking capacity at 230 V?

The C60H1P2AD has a rated Icu of 15 kA at 230...240 V AC, 50/60 Hz, conforming to IEC 60947-2.

What does the D curve mean on this breaker?

The D curve means the magnetic trip threshold is 10 to 14 times the rated current (2 A), so it tolerates the high inrush of motor or transformer loads without nuisance tripping.

Where can I buy C60H1P2AD?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C60H1P2AD