The Schneider Electric C60H1P2AD is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 2 A with a D tripping curve. The thermal-magnetic trip unit handles the overload side; the magnetic element handles short-circuit.
Breaking capacity and service continuity
Rated Icu of 15 kA at 230...240 V AC and 4 kA at 400...415 V AC, both per IEC 60947-2. At 60 V DC the Icu is 20 kA (1P), and at 130 V AC it reaches 30 kA. The limitation class is 3, so it lets through less fault energy than a standard Class 2 breaker, reducing stress on downstream components.
Snaps onto 35 mm symmetrical DIN rail, occupies 2 modules (18 mm per pitch). Depth is 73 mm, height 81 mm. Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, with 95 % relative humidity at 55 °C. Tropicalisation per IEC 60068-1 is included — the breaker is treated for warm, humid environments without condensation inside the enclosure. Operating altitude is rated to 2000 m.