Skip to main content
Schneider Electric C60H1P32AC — 1-Pole MCB (DIN Rail)

Schneider Electric C60H1P32AC C60 MCB, 32 A, C-Curve, 1P, 15

MPNC60H1P32AC
Obsolete

Schneider Electric C60H1P32AC, Multi9 C60 series, miniature circuit breaker, 1P, 32 A, C-curve, 15 kA breaking capacity at 230 V AC, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P32AC — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P32AC — Electrical & Protection
ParameterValue
Rated current (In)32 A at 30 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P32AC — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m
C60H1P32AC — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P32AC — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

Integrator's spec recap — C60H1P32AC

The Schneider Electric C60H1P32AC is a 1-pole C60H miniature circuit breaker from the Multi9 range, rated 32 A at 30 °C with a C-curve (magnetic trip between 5 and 10 times In). It fits a 35 mm symmetrical DIN rail, occupies 2 x 9 mm pitches (18 mm wide), and is suitable for isolation per IEC 60947-2.

Breaking capacity is 15 kA Icu at 230…240 V AC (50/60 Hz) per IEC 60947-2, with a corresponding Ics of 15 kA at 12…440 V AC — meaning the breaker can be reclosed after clearing a fault at that level without replacement. For DC circuits, the 1-pole unit delivers 20 kA Icu at 60 V DC.

Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible conductors; strip length is 14 mm, tightening torque 3.5 N·m. The toggle actuator provides local ON/OFF indication with a contact position indicator.

Frequently asked questions

How do I get current pricing and availability for C60H1P32AC?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; the part is sourced to order against an RFQ.

What is C60H1P32AC's listed depth?

The C60H1P32AC has a depth of 73 mm, a height of 81 mm, and a width of 18 mm (2 x 9 mm pitches).

What compliance documentation does this brand provide for C60H1P32AC?

The C60H1P32AC is certified to IEC 60947-2, with a declaration of conformity covering the standard's requirements for breaking capacity, isolation suitability, and impulse withstand voltage. It also meets tropicalisation class 2 per IEC 60068-1.

MPN
C60H1P32AC