Schneider Electric C60H1P32AD — 1-Pole MCB (DIN Rail)

Schneider Electric C60H1P32AD MCB, 32 A, D Curve, 1P, Multi9

MPNC60H1P32AD
Obsolete

Schneider Electric Multi9 C60H, C60H1P32AD, miniature circuit breaker, 1P, 32 A, D curve, 15 kA breaking capacity at 230-240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P32AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P32AD — Electrical & Protection
ParameterValue
Rated current (In)32 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P32AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m
C60H1P32AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P32AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The Schneider Electric C60H1P32AD is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 32 A at 40 °C with a D tripping curve. It is a thermal-magnetic MCB, meaning the bimetal handles overloads and the solenoid handles short-circuits, all in a single 18 mm wide DIN-rail module.

Rated breaking capacity hits 15 kA Icu at 230–240 V AC (IEC 60947-2), with a corresponding Ics of 15 kA at 12–440 V AC — meaning it can clear a fault and be reclosed at full rating. The 6 kV impulse withstand (Uimp) and 500 V insulation voltage (Ui) keep it coordinated with standard distribution gear.

Tunnel terminals accept up to 25 mm² flexible or 35 mm² rigid cable; strip length is 14 mm, tighten to 3.5 N·m.

Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, and 95 % relative humidity at 55 °C. Tropicalisation per IEC 60068-1 (2 levels) and limitation class 3 per IEC 60947-2.

Frequently asked questions

Where can I buy C60H1P32AD and get a price?

The C60H1P32AD is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the D curve on this MCB for?

The D curve (magnetic trip at 10–14 × In) is intended for loads with high inrush currents such as motor starters, small transformers, and discharge lighting, where a B or C curve would trip on startup.

What is the breaking capacity of C60H1P32AD?

The breaking capacity is 15 kA Icu at 230–240 V AC and 4 kA Icu at 400–415 V AC, both per IEC 60947-2. The service breaking capacity Ics is 15 kA at 12–440 V AC.

What compliance documentation does this brand provide for C60H1P32AD?

The C60H1P32AD is certified for isolation per IEC 60947-2, with tropicalisation per IEC 60068-1 and limitation class 3 per IEC 60947-2. Standard documentation includes the manufacturer's declaration of conformity; specific RoHS/REACH/UL status should be confirmed at time of order.

MPN