Schneider Electric C60H1P4AD C60 MCB, 1P, 4A, D Curve

MPNC60H1P4AD
Obsolete

Schneider Electric Multi9 C60, C60H1P4AD, miniature circuit breaker, 1-pole, 4 A rated current, D curve, 15 kA breaking capacity at 230 V AC, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P4AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P4AD — Electrical & Protection
ParameterValue
Rated current (In)4 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P4AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H1P4AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P4AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The Schneider Electric C60H1P4AD is a 1-pole miniature circuit breaker from the Multi9 C60 series, rated 4 A at 40 °C with a D tripping curve. The D curve means its magnetic trip operates between 10 and 14 times the rated current (40 to 56 A instantaneous trip), making it the right choice for loads with high inrush — think motor starters, small transformers, or discharge lighting where a B or C curve would nuisance-trip on startup. The thermal-magnetic trip unit handles the overload side. Breaking capacity is 15 kA Icu at 230...240 V AC (IEC 60947-2), which covers most commercial and light industrial distribution panels. At 400...415 V AC the rating drops to 4 kA — still adequate for sub-distribution in a 400 V system where the upstream device limits fault current.

The 18 mm width (2 x 9 mm pitches) means it occupies a single module slot in a standard distribution board — no surprises for panel fill calculations. Depth is 73 mm, height 81 mm. Tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible cable; strip length is 14 mm, tighten to 2 N·m.

Rated operational voltage (Ue): 440 V AC. Rated insulation voltage (Ui): 500 V AC. Impulse withstand (Uimp): 6 kV. Tropicalisation class 2 per IEC 60068-1, limitation class 3 per IEC 60947-2. Operating temperature range -25 to 60 °C, storage -40 to 70 °C. Mechanical durability: 20,000 cycles.

Frequently asked questions

How do I get current pricing and availability for C60H1P4AD?

The C60H1P4AD is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability.

What is the D curve on this MCB for?

The D curve trips magnetically at 10 to 14 times the rated current, so it handles high inrush loads like motor starters, small transformers, and discharge lighting without nuisance tripping on startup.

What compliance documentation does this brand provide for C60H1P4AD?

The C60H1P4AD is designed and tested to IEC 60947-2, with tropicalisation per IEC 60068-1. Standard Schneider documentation includes the datasheet, IEC declaration of conformity, and environmental compliance data (RoHS, REACH).