Skip to main content
Schneider Electric C60H1P6AB — 1-Pole MCB (DIN Rail)

Schneider Electric C60H1P6AB MCB, B Curve, 6 A, 1 Pole, 15 k

MPNC60H1P6AB
Obsolete

Schneider Electric Multi9 C60H1P6AB, C60H miniature circuit breaker, B curve, 6 A, 1 pole, 15 kA breaking capacity at 230 V AC, 2 modules wide.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P6AB — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P6AB — Electrical & Protection
ParameterValue
Rated current (In)6 A at 30 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P6AB — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H1P6AB — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P6AB — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The C60H1P6AB is a 1-pole miniature circuit breaker from Schneider Electric's Multi9 C60 range, rated 6 A with a B tripping curve (3–5 × In magnetic trip). That 15 kA Ics rating — the service breaking capacity — matches the Icu at 230 V, so it can reclose after a fault at that level without derating.

At 18 mm wide (2 modules at 9 mm pitch), it occupies two standard positions in the enclosure — plan your gland-plate fill and busbar alignment accordingly. The toggle gives local ON/OFF indication with a contact position indicator, so a quick glance confirms isolation status without metering.

Limitation class 3 per IEC 60947-2 limits let-through energy, which helps with downstream coordination.

Frequently asked questions

What is C60H1P6AB's listed depth (73 mm) on this component line?

The depth is 73 mm, which is the dimension from the DIN-rail mounting face to the front of the toggle. Combined with the 81 mm height and 18 mm width, it fits standard distribution board cutouts.

What is C60H1P6AB's listed range (Multi9) on this component line?

It belongs to the Multi9 range, Schneider Electric's residential and light-commercial MCB family. Within that, the product name is C60 and the device short name is C60H — the 'H' denotes the higher breaking capacity variant (15 kA at 230 V AC).

MPN
C60H1P6AB