The C60H1P6AC is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 6 A with a C tripping curve (magnetic trip between 5 and 10 x In). For a 6 A branch circuit in a distribution panel, that gives substantial fault-current headroom. The thermal-magnetic trip unit combines a bimetal strip for overload protection (time-delayed) with a solenoid for instantaneous short-circuit protection. The 1-pole format protects one line conductor, suitable for single-phase sub-circuits or for individual phase protection in three-phase panels where each pole is a separate breaker.
The fixed mounting mode means it clips into the rail and stays; no DIN-rail busbar adapter needed for the breaker itself. The ON/OFF toggle provides local indication; the contact position indicator confirms isolation status when used as a disconnector (suitability for isolation per IEC 60947-2).
Regulatory and environmental
Rated insulation voltage 500 V AC, operational voltage 440 V AC, impulse withstand 6 kV — all per IEC 60947-2. Storage range -40 to 70 °C; operating ambient -25 to 60 °C.