C60H1P6AC MCB, C Curve, 6 A, 1P, 15 kA, Multi9

MPNC60H1P6AC
Obsolete

Schneider Electric Multi9 C60H series, C60H1P6AC, miniature circuit breaker, 1 pole, 6 A, C curve, 15 kA breaking capacity at 230 V AC, thermal-magnetic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H1P6AC — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60H1P6AC — Electrical & Protection
ParameterValue
Rated current (In)6 A at 30 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H1P6AC — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H1P6AC — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H1P6AC — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The C60H1P6AC is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 6 A with a C tripping curve (magnetic trip between 5 and 10 x In). For a 6 A branch circuit in a distribution panel, that gives substantial fault-current headroom. The thermal-magnetic trip unit combines a bimetal strip for overload protection (time-delayed) with a solenoid for instantaneous short-circuit protection. The 1-pole format protects one line conductor, suitable for single-phase sub-circuits or for individual phase protection in three-phase panels where each pole is a separate breaker.

The fixed mounting mode means it clips into the rail and stays; no DIN-rail busbar adapter needed for the breaker itself. The ON/OFF toggle provides local indication; the contact position indicator confirms isolation status when used as a disconnector (suitability for isolation per IEC 60947-2).

Regulatory and environmental

Rated insulation voltage 500 V AC, operational voltage 440 V AC, impulse withstand 6 kV — all per IEC 60947-2. Storage range -40 to 70 °C; operating ambient -25 to 60 °C.

Frequently asked questions

Where can I buy C60H1P6AC and how do I get a price?

The C60H1P6AC is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is C60H1P6AC's rated breaking capacity?

The C60H1P6AC has a 15 kA Icu at 230...240 V AC 50/60 Hz per IEC 60947-2. At 400...415 V AC the breaking capacity is 4 kA Icu. The Ics (service breaking capacity) is 15 kA at 12...440 V AC.

What compliance documentation does Schneider provide for C60H1P6AC?

The C60H1P6AC carries IEC 60947-2 certification for breaking capacity, insulation voltage, and impulse withstand. Tropicalisation per IEC 60068-1 class 2 is documented. For RoHS, REACH, and UL documentation, the manufacturer's standard compliance declarations apply — confirm specific certs at time of order.