Skip to main content
Schneider Electric C60H2P1AD — 1-Pole MCB (DIN Rail)

Schneider Electric C60H2P1AD MCB, 1P+N, 1 A, D Curve, 10 kA

MPNC60H2P1AD
Obsolete

Schneider Electric Multi9 C60H miniature circuit breaker, 1P+N, 1 A rated current, D curve, 10 kA breaking capacity at 440 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P1AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
C60H2P1AD — Electrical & Protection
ParameterValue
Rated current (In)1 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P1AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width36 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H2P1AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H2P1AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The Schneider Electric C60H2P1AD is a 1P+N miniature circuit breaker from the Multi9 C60 range, rated 1 A at 40 °C with a D tripping curve (magnetic trip 10–14 x In). It breaks up to 10 kA at 440 V AC (Icu per IEC 60947-2) and 30 kA at 230–240 V AC, so it can handle high-fault downstream of a distribution transformer without upstream coordination headaches.

Depth is 73 mm, so it clears most 80 mm-deep enclosures; height is 81 mm. The toggle gives positive ON/OFF indication, and the contact position indicator confirms isolation per IEC 60947-2.

Frequently asked questions

What is the breaking capacity of C60H2P1AD?

The C60H2P1AD has a breaking capacity of 10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, and 30 kA at 230–240 V AC, all conforming to IEC 60947-2.

What is the D curve and why does it matter?

The D curve means the magnetic trip activates at 10–14 times the rated current (1 A), so it allows high inrush from motor or transformer loads without nuisance tripping — not ideal for resistive loads.

Where can I buy C60H2P1AD?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C60H2P1AD