The C60H2P2AD is a 2 A D-curve miniature circuit breaker from the Schneider Multi9 C60H series, configured 1P+N — one protected pole plus a switched neutral on the left. The 2 A rating at 40 °C means it carries 2 A continuously in a 40 °C ambient; above that temperature, derate per IEC 60898. Breaking capacity hits 30 kA at 230-240 V AC, 15 kA at 400-415 V AC, and 10 kA at 440 V AC — all per IEC 60947-2, so it clears faults up to those levels without upstream coordination failure. Limitation class 3 (energy-limiting) means it restricts let-through energy enough to protect downstream equipment in a properly coordinated panel.
The 73 mm depth leaves clearance for standard enclosure depths. Neutral lands on the left-side terminal. The toggle provides local ON/OFF indication and a contact position indicator confirms isolation status — the breaker is certified for isolation per IEC 60947-2. Earth-leakage protection requires a separate Vigi block, not integrated.