Skip to main content
Schneider Electric C60H2P32AC — 1-Pole MCB (DIN Rail)

Schneider C60H2P32AC MCB, C Curve 32 A 1P+N, 10 kA

MPNC60H2P32AC
Obsolete

Schneider Electric, Multi9 range, C60H miniature circuit breaker, C60H2P32AC, 1P+N, 32 A, C curve, 10 kA at 440 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P32AC — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
C60H2P32AC — Electrical & Protection
ParameterValue
Rated current (In)32 A at 30 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P32AC — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width36 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m
C60H2P32AC — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H2P32AC — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The C60H2P32AC is a 1P+N miniature circuit breaker from the Schneider Multi9 range, rated 32 A at 30 °C with a C curve (magnetic trip at 5–10× In). Breaking capacity hits 10 kA Icu at 440 V AC (IEC 60947-2), 15 kA at 400–415 V, and 30 kA at 230–240 V — enough for most commercial and light industrial distribution panels. The 1P+N configuration switches the phase and provides a switched neutral, which is common in single-phase final subcircuits where isolating both conductors is required. The thermal-magnetic trip unit gives overload protection via a bimetal strip and short-circuit protection via a solenoid.

Earth-leakage protection requires a separate block — not integrated.

Frequently asked questions

Where can I buy C60H2P32AC and get a price?

The C60H2P32AC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C60H2P32AC?

The C60H2P32AC has a breaking capacity of 10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, 25 kA at 125 V DC (2P), and 30 kA at 230–240 V AC, all conforming to IEC 60947-2.

What is the closest alternative to C60H2P32AC in the same family?

Within the Multi9 C60 range, the closest peer is the C60H-DC variant for DC circuits, or the C60N/C60L versions which differ in breaking capacity (lower for C60N, higher for C60L). The C60H2P32AC is the 32 A, C-curve, 1P+N, 10 kA variant — the main deciding factor is the required SCCR at your system voltage.

MPN