Schneider Electric C60H2P40AD — 1-Pole MCB (DIN Rail)

Schneider Electric C60H2P40AD C60 MCB, 1P+N, 40 A, D Curve

MPNC60H2P40AD
Obsolete

Schneider Electric Multi9 C60 series, C60H2P40AD miniature circuit breaker, 1P+N, 40 A rated current, D curve, thermal-magnetic trip, 10-30 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P40AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
C60H2P40AD — Electrical & Protection
ParameterValue
Rated current (In)40 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P40AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width36 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)3.5 N.m
C60H2P40AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H2P40AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The C60H2P40AD is a Schneider Electric Multi9 C60-series miniature circuit breaker — a 1P+N thermal-magnetic MCB rated 40 A at 40 °C with a D tripping curve. The 1P+N pole arrangement protects one phase and switches the neutral; the neutral pole is not protected, so this is a distribution MCB, not a main isolator for a 2-pole load. Breaking capacity runs 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC — the 10 kA at 440 V is the limiting figure for a 400 V line-to-line feed. The 15 kA at 400–415 V gives headroom above the typical 10 kA utility fault level in most commercial panels.

The 36 mm width at 4 module pitches occupies four 9 mm slots, so plan for 4 × 9 = 36 mm of rail space per unit. Depth is 73 mm, height 81 mm. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible; strip 14 mm and torque to 3.5 N·m. The neutral position is left. Toggle control with ON/OFF indication and a contact position indicator.

Frequently asked questions

Where can I buy the C60H2P40AD and get a price?

The C60H2P40AD is sourced to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here.

What does the D curve mean on this breaker?

The D curve sets the magnetic trip threshold at 10–14× the rated current, so for a 40 A breaker, instantaneous trip occurs between 400 A and 560 A. This is designed for loads with high inrush, such as small motors, transformers, or welding equipment, where a B or C curve would trip on startup.

What compliance documentation does the C60H2P40AD carry?

The breaker is certified to IEC 60947-2 and IEC 60068-1 for tropicalisation. It is suitable for isolation per IEC 60947-2. The evidence does not list UL, CSA, RoHS, or REACH declarations — confirm with the supplier at quote time.