Skip to main content
Schneider Electric C60H2P4AD — 1-Pole MCB (DIN Rail)

Schneider Electric C60H2P4AD Multi9 C60 MCB, D Curve, 4 A, 1

MPNC60H2P4AD
Obsolete

Schneider Electric Multi9 C60 series, C60H2P4AD miniature circuit breaker, 1P+N, D curve, 4 A rated, 30 kA breaking capacity at 230-240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P4AD — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
C60H2P4AD — Electrical & Protection
ParameterValue
Rated current (In)4 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P4AD — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width36 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2 N.m
C60H2P4AD — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
C60H2P4AD — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2

Product details

The Schneider Electric C60H2P4AD is a Multi9 C60 series miniature circuit breaker (MCB) with a D tripping curve, rated 4 A at 40 °C. It protects a single pole plus neutral (1P+N) in AC distribution circuits. Breaking capacity reaches 30 kA Icu at 230-240 V AC, 15 kA at 400-415 V AC, and 10 kA at 440 V AC, all conforming to IEC 60947-2.

Mounts on a 35 mm symmetrical DIN rail (EN 60715), occupying 4 modular pitches of 9 mm each — 36 mm total width. Dimensions: 81 mm height, 36 mm width, 73 mm depth.

Tropicalisation level 2 per IEC 60068-1 means the breaker is treated against humidity and fungal growth — relevant for installations in warm, damp environments. Limitation class 3 per IEC 60947-2 indicates the let-through energy (I²t) is limited, reducing stress on downstream components during a fault.

Frequently asked questions

Where can I buy the C60H2P4AD and get a price?

The C60H2P4AD is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of the C60H2P4AD?

Breaking capacity is 30 kA Icu at 230-240 V AC, 15 kA at 400-415 V AC, and 10 kA at 440 V AC, all per IEC 60947-2. At 125 V DC (2 poles in series) it is rated 25 kA Icu.

What compliance documentation is available for the C60H2P4AD?

The breaker carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation per IEC 60068-1 level 2 is confirmed. RoHS, REACH, and UL documentation should be verified against the specific manufacturing date code — contact your sourcing desk for the compliance pack matching your lot.

MPN
C60H2P4AD