Schneider Electric C60H2P50AB — 2-Pole MCB (DIN Rail)

Schneider C60H2P50AB MCB, 50A, Curve B, 2P, 10kA

MPNC60H2P50AB
Obsolete

Schneider Electric Multi9 C60H, C60H2P50AB, miniature circuit breaker, 50 A, B-curve, 2-pole, 10 kA Icn per EN 60898, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P50AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H2P50AB — Electrical
ParameterValue
Rated current [In]50 A at 30 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)DC AC
Network frequency50/60 Hz
C60H2P50AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P50AB — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H2P50AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H2P50AB — Approvals
ParameterValue
Standards / complianceIEC 60947-2 EN 60898

Product details

The Schneider Electric C60H2P50AB is a 2-pole miniature circuit breaker from the Multi9 C60H range, rated 50 A with a B-curve trip characteristic.

The C60H2P50AB carries a 10 kA Icn rating at 230/400 V AC per EN 60898 — that's the standard for domestic and commercial final circuits. Under IEC 60947-2, the Icu (ultimate breaking capacity) goes higher: 15 kA at 400–415 V AC, 25 kA at 125 V DC (2-pole series trip), and 30 kA at 230–240 V AC. The Ics (service breaking capacity) is 7.5 kA at 230/400 V AC per EN 60898, meaning it can clear a fault at that level and still be used again afterward. For a 50 A feeder, that gives decent selectivity with upstream devices rated 25 kA or higher — common in a sub-distribution board fed from a 100 A or 160 A MCCB.

The 2-pole body takes 4 modules of 9 mm pitch — 36 mm wide total, 81 mm tall, 73 mm deep. That's a standard footprint for a 2-pole MCB; it fits any DIN-rail enclosure or distribution board without surprises.

Frequently asked questions

How do I get current pricing and availability for C60H2P50AB?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock levels are confirmed at quote time.

What is C60H2P50AB's breaking capacity?

The Icn is 10 kA at 230/400 V AC per EN 60898. Under IEC 60947-2, the Icu reaches 15 kA at 400–415 V AC, 25 kA at 125 V DC (2-pole), and 30 kA at 230–240 V AC.

What does the B-curve mean on this breaker?

The magnetic trip threshold is 3 to 5 times the rated current (150–250 A for the 50 A version). That's suited for resistive or low-inrush loads — lighting, heating, control transformers — where a C-curve (5–10x) would be too slow to trip on a hard short.