The Schneider Electric C60H2P6AD is a thermal-magnetic miniature circuit-breaker from the Multi9 C60 range, 1P+N configuration, rated 6 A at 40 °C with a D tripping curve (magnetic trip at 10–14 × In). It protects branch circuits against overload and short-circuit faults in AC distribution panels.
Breaking capacity: 10 kA Icu at 440 V AC (IEC 60947-2), with higher ratings at lower voltages — 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 25 kA at 125 V DC (2P). D curve magnetic trip operates at 10–14 × In. This suits loads with high inrush, such as small motors or transformers. Rated operational voltage 440 V AC, insulation voltage 500 V AC.
Width is 36 mm (4 × 9 mm pitches). Depth 73 mm, height 81 mm. Strip length 14 mm.