Skip to main content
Schneider Electric C60H3P10AC — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P10AC MCB, C Curve, 10 A, 3P, Multi9

MPNC60H3P10AC
Obsolete

Schneider Electric Multi9 C60H, C60H3P10AC, miniature circuit breaker, 3P, C curve, 10 A, 10 kA at 440 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60H3P10AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P10AC — Electrical
ParameterValue
Rated current [In]10 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P10AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P10AC — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P10AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P10AC is a C60H-series miniature circuit breaker from the Multi9 range, rated 10 A at 30 °C with a C trip curve (magnetic tripping between 5 and 10 times In). Three poles, thermal-magnetic trip unit, rated for distribution duty in a 35 mm symmetrical DIN-rail panel. Breaking capacity hits 30 kA Icu at 230...240 V AC and 10 kA Icu at 440 V AC, both per IEC 60947-2 — enough headroom for most commercial and light industrial sub-distribution boards.

The C curve means the magnetic trip fires between 5 and 10 times the 10 A rating (50–100 A instantaneous). That suits mixed resistive-inductive loads — lighting, small motor circuits, general-purpose socket outlets — where you need a short delay to ride through inrush without nuisance tripping. Three protected poles on a 3P device; the neutral is switched if you add the separate earth-leakage block. That's generous for a 10 A breaker — you can land larger feed conductors without adapter lugs.

Snaps onto 35 mm symmetrical DIN rail. Width is 54 mm (6 x 9 mm pitches), depth 73 mm, height 81 mm. Toggle actuator with ON/OFF indication and a contact position indicator for visual confirmation of the mechanical state.

Frequently asked questions

What is C60H3P10AC's breaking capacity?

30 kA Icu at 230...240 V AC and 10 kA Icu at 440 V AC, both per IEC 60947-2. The service breaking capacity Ics is 15 kA at 12...440 V AC.

What compliance documentation does Schneider provide for C60H3P10AC?

The breaker is certified to IEC 60947-2, with tropicalisation per IEC 60068-1. It carries suitability for isolation marking per IEC 60947-2.

MPN