Skip to main content
Schneider Electric C60H3P16AD — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P16AD MCB, D Curve, 16 A, 3P, Multi9

MPNC60H3P16AD
Obsolete

Schneider Electric Multi9 C60H C60H3P16AD, miniature circuit breaker, 3P, D curve, 16 A at 40 °C, 10-40 kA breaking capacity per IEC 60947-2, thermal-magnetic trip, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60H3P16AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P16AD — Electrical
ParameterValue
Rated current [In]16 A at 40 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P16AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P16AD — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P16AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The C60H3P16AD is a 3-pole miniature circuit breaker from the Multi9 C60H range, rated 16 A at 40 °C with a D trip curve. The D curve means the magnetic trip operates at 10 to 14 times the rated current (10...14 x In) — designed for loads with high inrush, like motor starters, transformers, or discharge lighting, where a B or C curve would nuisance-trip on startup. The 16 A rating at 40 °C is the continuous current it carries without tripping in a 40 °C ambient; derate for higher panel temperatures per the thermal curve. Breaking capacity is specified per IEC 60947-2: 30 kA Icu at 230...240 V AC, 15 kA at 400...415 V AC, and 10 kA at 440 V AC. Mounts on a 35 mm symmetrical DIN rail, occupies 6 x 9 mm pitches (54 mm wide). The tunnel terminals accept up to 25 mm² rigid or 16 mm² flexible copper, with a 2 N·m tightening torque and 14 mm strip length.

Deployment context

The 54 mm width (6 modules) fits standard enclosure cutouts. Rated for operation from -25 to 60 °C ambient, storage from -40 to 70 °C, and 95 % relative humidity at 55 °C with tropicalisation class 2 per IEC 60068-1 — suitable for unconditioned electrical rooms or outdoor-rated enclosures in humid climates.

Frequently asked questions

Where can I buy C60H3P16AD and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of C60H3P16AD at 400 V?

The breaking capacity (Icu) is 15 kA at 400...415 V AC per IEC 60947-2. The service breaking capacity (Ics) at that voltage is also 15 kA.

What does the D curve mean on this breaker?

The D curve means the magnetic trip threshold is 10 to 14 times the rated current (10...14 x In). This suits loads with high inrush current such as motors, transformers, and discharge lighting, where a B or C curve would trip on startup.

MPN