Skip to main content
Schneider Electric C60H3P20AC — 2-Pole MCB (DIN Rail)

Schneider C60H3P20AC MCB, 20A C-Curve, 3P, 10kA

MPNC60H3P20AC
Obsolete

Schneider Electric Multi9 C60H, MCB, 3P, 20 A, C-curve, 10 kA Icu at 440 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60H3P20AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P20AC — Electrical
ParameterValue
Rated current [In]20 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P20AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P20AC — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P20AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P20AC is a 3-pole Miniature Circuit-Breaker (MCB) from the Multi9 C60 range, rated 20 A at 30 °C with a C-curve trip characteristic (magnetic tripping limit 5...10 x In).

Breaking capacity and ratings

Breaking capacity is 10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2, with higher ratings at lower voltages: 15 kA at 400...415 V AC, 25 kA at 125 V DC (2P), 30 kA at 230...240 V AC, and 40 kA at 125 V DC (3P).

Construction and environment

Maximum operating altitude is 2000 m.

Frequently asked questions

What is the breaking capacity of C60H3P20AC?

The breaking capacity is 10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2, with higher ratings at lower voltages (e.g., 30 kA at 230...240 V AC).

Where can I buy C60H3P20AC?

It is sourced and quoted to order against an RFQ through independent distribution. Availability and pricing are confirmed at quote time.

What is the closest alternative to C60H3P20AC in the same family?

Within the Multi9 C60 range, the primary difference between variants is the rated current (In) and the number of poles. The C60H3P20AC is a 20 A, 3-pole, C-curve unit; a 1-pole or 2-pole version, or a different current rating (e.g., 16 A or 32 A), would be the closest parametric alternative but is not pin-compatible due to different pole count and width.

What compliance documentation is available for C60H3P20AC?

The breaker is designed to conform to IEC 60947-2 and IEC 60068-1 (tropicalisation class 2). It carries the CE mark as a Schneider Electric product. Specific RoHS/REACH declarations and UL listing status should be confirmed from the manufacturer's documentation at the time of order.

MPN
C60H3P20AC