The Schneider Electric C60H3P25AB is a 3-pole miniature circuit breaker from the Multi9 C60 range, rated 25 A with a B-curve trip characteristic.
Depth is 73 mm, height 81 mm. The 14 mm strip length is standard for this terminal class. The toggle gives a clear ON/OFF indication, and the contact position indicator confirms isolation status — useful when locking out for downstream work.
The C60H3P25AB carries a 30 kA Icu at 230–240 V AC and 10 kA at 440 V AC, with a service breaking capacity (Ics) of 15 kA at 400–415 V. That Ics figure — 100% of Icu at the lower voltage — means the breaker can be reclosed after a fault at that level without immediate replacement, which matters for uptime in continuous-process panels. The B-curve (3–5× In magnetic trip) coordinates well with upstream S-curve or selective breakers in a typical two-level distribution scheme.
Tropicalisation level 2 per IEC 60068-1 handles 95% RH at 55 °C. Limitation class 3 per IEC 60947-2 means it lets through limited energy under short-circuit — helps protect downstream equipment.