C60H3P2AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P2AC — Electrical
ParameterValue
Rated current [In]2 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P2AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P2AC — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P2AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P2AC is a 3-pole miniature circuit breaker from the Multi9 C60 family, rated 2 A at 30 °C with a C-curve trip characteristic (magnetic trip between 5 and 10 times In). It's a thermal-magnetic MCB meant for distribution boards — the kind of thing you'd snap onto a 35 mm symmetrical DIN rail in a panel feeding lighting, general-purpose outlets, or small motor circuits where you want moderate inrush tolerance without going to a D-curve. The 3-pole version (3P) handles three-phase AC networks at 440 V AC 50/60 Hz.

This breaker carries multiple Icu ratings depending on voltage: 30 kA at 230-240 V AC, 15 kA at 400-415 V AC, and 10 kA at 440 V AC — all per IEC 60947-2. For a 2 A MCB on a 400 V three-phase supply, the 15 kA Icu is the figure you'd use for selectivity studies upstream.

Mounting and integration notes

Occupies 6 x 9 mm pitches = 54 mm width. The toggle gives local ON/OFF indication. For earth-leakage protection, a separate RCD block is required — this MCB doesn't include integral GFCI.

Environmental and compliance details

Limitation class 3 per IEC 60947-2 — energy let-through is limited, which helps with downstream cable protection.

Frequently asked questions

What is the breaking capacity of C60H3P2AC at 400 V?

At 400-415 V AC, the Icu is 15 kA per IEC 60947-2. At 440 V AC it's 10 kA, and at 230-240 V AC it's 30 kA.

What does the C-curve mean on this breaker?

The C-curve means the magnetic trip operates between 5 and 10 times the rated current (In). For a 2 A breaker, that's 10 to 20 A instantaneous trip — suited for general-purpose loads with moderate inrush like lighting or small motors.

Where can I buy C60H3P2AC and how is it quoted?

We source the C60H3P2AC to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does Schneider provide for C60H3P2AC?

The breaker carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation per IEC 60068-1 class 2 is documented. For RoHS, REACH, and UL specifics, the manufacturer's declaration is available on request.

MPN
C60H3P2AC