Skip to main content
Schneider Electric C60H3P2AD — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P2AD C60 MCB, 3P, D Curve, 2 A, 10 k

MPNC60H3P2AD
Obsolete

Schneider Electric Multi9 C60 series, C60H3P2AD, 3-pole miniature circuit-breaker, D curve, 2 A rated current, 10 kA breaking capacity at 440 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60H3P2AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P2AD — Electrical
ParameterValue
Rated current [In]2 A at 40 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P2AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P2AD — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P2AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P2AD is a 3-pole miniature circuit-breaker from the Multi9 range, rated 2 A at 40 °C with a D tripping curve (magnetic threshold 10–14 × In). The breaking capacity reaches 30 kA Icu at 230–240 V AC and 10 kA Icu at 440 V AC (per IEC 60947-2), so it can interrupt fault currents up to that level without welding contacts or cascading upstream. Thermal-magnetic trip technology handles both overload (thermal bimetal) and short-circuit (solenoid) protection in one unit.

Depth is 73 mm, height 81 mm. The toggle gives local ON/OFF indication and a contact-position indicator confirms isolation status.

Tropicalisation level 2 per IEC 60068-1 and limitation class 3 per IEC 60947-2 — the latter means it limits let-through energy for downstream equipment. Relative humidity tolerance of 95 % at 55 °C suits non-condensing environments like enclosed panels near washdown areas.

Frequently asked questions

What is the breaking capacity of C60H3P2AD?

The breaking capacity (Icu) is 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC, all per IEC 60947-2. Service breaking capacity (Ics) is 15 kA at 12–440 V AC.

MPN
C60H3P2AD