The Schneider Electric C60H3P2AD is a 3-pole miniature circuit-breaker from the Multi9 range, rated 2 A at 40 °C with a D tripping curve (magnetic threshold 10–14 × In). The breaking capacity reaches 30 kA Icu at 230–240 V AC and 10 kA Icu at 440 V AC (per IEC 60947-2), so it can interrupt fault currents up to that level without welding contacts or cascading upstream. Thermal-magnetic trip technology handles both overload (thermal bimetal) and short-circuit (solenoid) protection in one unit.
Depth is 73 mm, height 81 mm. The toggle gives local ON/OFF indication and a contact-position indicator confirms isolation status.
Tropicalisation level 2 per IEC 60068-1 and limitation class 3 per IEC 60947-2 — the latter means it limits let-through energy for downstream equipment. Relative humidity tolerance of 95 % at 55 °C suits non-condensing environments like enclosed panels near washdown areas.