32 A C-curve MCB for distribution panels
The Schneider Electric C60H3P32AC is a C60H-series miniature circuit breaker rated at 32 A with a C-curve trip characteristic (5–10 x In magnetic tripping limit), 3 protected poles, and a 10 kA Icu breaking capacity at 440 V AC.
The C60H3P32AC delivers 30 kA Icu at 230–240 V AC and 15 kA Ics at 12–440 V AC. That Ics rating — the service breaking capacity — tells you what it can clear repeatedly without replacing the breaker. At 230 V the 30 kA Icu gives solid selectivity headroom downstream of a higher-rated upstream device, so a fault on a branch outlet won't take the whole panel down.
Snaps onto 35 mm symmetrical DIN rail, occupies 6 x 9 mm pitches (54 mm wide), with a depth of 73 mm and height of 81 mm. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible cable; strip length is 14 mm and tightening torque is 3.5 N·m. That footprint fits standard distribution boards without crowding adjacent breakers or leaving too little bending radius for the incoming cable.