Skip to main content
Schneider Electric C60H3P3AC — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P3AC C60 MCB, 3P, 3 A, C Curve, 10-4

MPNC60H3P3AC
Obsolete

Schneider Electric Multi9 C60 C60H3P3AC miniature circuit breaker, 3-pole, 3 A, C curve, thermal-magnetic trip, breaking capacity 10-40 kA, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60H3P3AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P3AC — Electrical
ParameterValue
Rated current [In]3 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P3AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P3AC — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P3AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P3AC is a 3-pole miniature circuit breaker from the Multi9 C60 range, rated 3 A at 30 °C with a C curve (magnetic trip 5–10 x In). It is a thermal-magnetic trip unit, so it handles both overload and short-circuit protection in one device.

Breaking capacity and ratings

Breaking capacity varies by voltage: 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC (all per IEC 60947-2).

Occupies 6 x 9 mm pitches (54 mm wide), 81 mm tall, 73 mm deep. Strip length 14 mm. The toggle handle gives local ON/OFF indication and a contact position indicator confirms isolation status (suitable for isolation per IEC 60947-2).

Frequently asked questions

What is the breaking capacity of C60H3P3AC?

The C60H3P3AC has a breaking capacity (Icu) of 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC per IEC 60947-2. Service breaking capacity (Ics) is 15 kA at 12–440 V AC.

Where can I buy C60H3P3AC?

The C60H3P3AC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the depth of C60H3P3AC?

The depth is 73 mm.

What range does C60H3P3AC belong to?

It belongs to the Schneider Electric Multi9 C60 range.

What compliance documentation is available for C60H3P3AC?

The breaker carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation conforms to IEC 60068-1 (class 2). The evidence does not list RoHS, REACH, or UL documentation specifically for this order code.

MPN