The C60H3P40AD is a 40 A, 3-pole miniature circuit-breaker from the Multi9 C60H family, with a D tripping curve (10–14 x In magnetic trip threshold). The 40 A rating at 40 °C and the 10 kA Icu at 440 V AC mean it handles fault currents up to 10 kA at that voltage, which covers most distribution panels in industrial and commercial buildings. For a panel builder, the 35 mm DIN rail mount and 54 mm width (6 x 9 mm pitches) slot into standard distribution boards without surprises.
Deployment context
Snaps onto 35 mm symmetrical DIN rail — standard for panel and enclosure mounting. The tunnel terminals accept up to 25 mm² flexible or 35 mm² rigid, with a 3.5 N.m tightening torque and 14 mm strip length. That's enough lug for a 40 A feeder in a sub-distribution board. Earth-leakage protection requires a separate block — not integrated, so plan for a Vigi add-on if you need RCD.