Skip to main content
Schneider Electric C60H3P50AB — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P50AB MCB, 50A B Curve, 3P, Multi9

MPNC60H3P50AB
Obsolete

Schneider Electric Multi9 C60H, C60H3P50AB, miniature circuit breaker, 3P, 50 A, B curve, 10-40 kA breaking capacity, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H3P50AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P50AB — Electrical
ParameterValue
Rated current [In]50 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P50AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P50AB — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P50AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The C60H3P50AB is a 3-pole miniature circuit breaker from the Schneider Electric Multi9 C60H series, rated 50 A at 30 °C with a B tripping curve (3–5 × In magnetic trip). Breaking capacity varies by voltage: 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC, all per IEC 60947-2. Rated operational voltage is 440 V AC, insulation voltage 500 V AC. The 3 protected poles handle three-phase distribution (, L2, L3) with a separate earth-leakage block if needed. Isolation capability is confirmed per IEC 60947-2 — the toggle provides visible ON/OFF indication and a contact position indicator.

Width is 54 mm (6 × 9 mm pitches), depth 73 mm, height 81 mm — occupies 3 standard module spaces. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible cable; strip length 14 mm, tightening torque 3.5 N·m. Limitation class 3 per IEC 60947-2 limits let-through energy, helping downstream coordination.

Frequently asked questions

Where can I buy C60H3P50AB and how do I get a price?

The C60H3P50AB is available to order through independent distribution. Submit an RFQ to confirm current pricing and availability — no stock count or price is published here.

What is the breaking capacity of C60H3P50AB at 400 V?

At 400–415 V AC, the C60H3P50AB has a rated ultimate breaking capacity (Icu) of 15 kA and a service breaking capacity (Ics) of 15 kA, both per IEC 60947-2.

What compliance documentation does this brand provide for C60H3P50AB?

The C60H3P50AB is designed to IEC 60947-2 (breaking capacity, isolation, limitation class) and IEC 60068-1 (tropicalisation). It carries the Schneider Electric Multi9 brand approvals — typically UL, CSA, CE, and UKCA, though specific marks should be verified against the unit's label.

MPN