Skip to main content
Schneider Electric C60H3P63AD — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P63AD C60H MCB, 63 A, D Curve, 3P

MPNC60H3P63AD
Obsolete

Schneider Electric Multi9 C60H, C60H3P63AD, miniature circuit breaker, 63 A, D curve, 3 poles, 30 kA breaking capacity at 230-240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H3P63AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P63AD — Electrical
ParameterValue
Rated current [In]63 A at 40 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P63AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P63AD — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P63AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

What this MCB does and where it fits

The Schneider Electric C60H3P63AD is a C60H-series miniature circuit breaker from the Multi9 range, rated 63 A at 40 °C with a D tripping curve (magnetic trip threshold 10–14 × In).

Breaking capacity and what it means for your panel

The C60H3P63AD delivers 30 kA Icu at 230–240 V AC and 15 kA Icu at 400–415 V AC, both per IEC 60947-2. For a panel fed by a transformer with a high short-circuit rating, this breaker stays within its interrupting envelope without needing a current-limiting upstream fuse.

Snaps onto 35 mm DIN rail — 6 module pitches (9 mm each) wide, 54 mm total width, 81 mm tall, 73 mm deep. The toggle gives ON/OFF indication, and there's a contact position indicator for isolation verification (suitable for isolation per IEC 60947-2). Earth-leakage protection is handled by a separate block, not integrated.

Frequently asked questions

What is the breaking capacity of C60H3P63AD at 230 V?

30 kA Icu at 230–240 V AC 50/60 Hz per IEC 60947-2. At 400–415 V AC it's 15 kA Icu.

What wire sizes does the C60H3P63AD accept?

Tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible copper. Strip length is 14 mm, torque to 3.5 N·m.

MPN
C60H3P63AD