Skip to main content
Schneider Electric C60H3P6AB — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P6AB Miniature Circuit Breaker, 6 A,

MPNC60H3P6AB
Obsolete

Schneider Electric Multi9 C60H series, C60H3P6AB, miniature circuit breaker, 3 poles, 6 A rated current, B curve, 10 kA breaking capacity at 440 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H3P6AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P6AB — Electrical
ParameterValue
Rated current [In]6 A at 30 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P6AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P6AB — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P6AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The Schneider Electric C60H3P6AB is a 3-pole miniature circuit breaker from the Multi9 C60H range, rated 6 A at 30 °C with a B tripping curve (3…5 x In magnetic trip). It breaks 10 kA Icu at 440 V AC and 30 kA at 230…240 V AC, per IEC 60947-2 — enough for most distribution sub-feeders in commercial or light industrial panels.

Rated Icu of 10 kA at 440 V AC, 15 kA at 400…415 V AC, and 30 kA at 230…240 V AC. That Ics/Icu ratio (50% at 440 V) is typical for a C60H; if your fault current is above 15 kA at the panel, you need to check coordination with the upstream device.

Fixed mounting, toggle control with ON/OFF indication. The 73 mm depth keeps it inside standard 100 mm enclosure depths.

Listed as current production (active lifecycle). No successor or phase-out notice on record.

Frequently asked questions

What is the breaking capacity of C60H3P6AB?

10 kA Icu at 440 V AC, 15 kA at 400…415 V AC, 30 kA at 230…240 V AC, all per IEC 60947-2. Service breaking capacity Ics is 15 kA across 12…440 V AC.

What is the rated current of C60H3P6AB?

6 A at 30 °C ambient.

MPN