Skip to main content
Schneider Electric C60H3P6AD — 2-Pole MCB (DIN Rail)

Schneider Electric C60H3P6AD C60 MCB, 6 A, D Curve, 3P, 10-4

MPNC60H3P6AD
Obsolete

Schneider Electric Multi9 C60 series, C60H3P6AD, 3-pole miniature circuit breaker, 6 A rated current, D curve, 10-40 kA breaking capacity, thermal-magnetic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H3P6AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H3P6AD — Electrical
ParameterValue
Rated current [In]6 A at 40 °C
Number of protected poles3
Pole configuration3P
Rated operational voltage [Ue]440 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
C60H3P6AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H3P6AD — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H3P6AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C

Product details

The C60H3P6AD is a 3-pole C60H miniature circuit breaker from the Multi9 range, rated 6 A at 40 °C with a D tripping curve (magnetic trip at 10–14 × In). The 6 A rating means it protects a branch circuit drawing up to 6 A continuous; for motor duty, that usually corresponds to a fractional-horsepower load or a control transformer primary. Breaking capacity is rated per IEC 60947-2: 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC.

The toggle mechanism provides ON/OFF local indication and a contact position indicator for visual confirmation of isolation. It's certified for isolation per IEC 60947-2, meaning you can safely use it as a disconnecting means for the downstream circuit during maintenance.

MPN
C60H3P6AD