Skip to main content
Schneider Electric C60H4P10AC

Schneider Electric C60H4P10AC MCB, C-Curve 10A 4P, 10kA

MPN C60H4P10AC
Obsolete

Schneider Electric Multi9 C60H series, C60H4P10AC miniature circuit breaker, 4-pole, C-curve, 10 A, 10 kA breaking capacity, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C60H4P10AC specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
Depth73 mm
Width72 mm
Height81 mm
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric C60H4P10AC is a 4-pole miniature circuit breaker (MCB) from the Multi9 C60H range, rated 10 A with a C-curve trip characteristic (5–10 × In magnetic trip).

Under IEC 60947-2 the Icu climbs to 15 kA at 400–415 V AC and 30 kA at 230–240 V AC — the higher industrial rating matters when the MCB sits in a panel with a larger upstream transformer. DC ratings hit 25 kA at 125 V (2-pole series) and 50 kA at 250 V (4-pole series), so this 4P unit can break DC faults at those levels. The Ics (service breaking capacity) is 7.5 kA at 230/400 V AC per EN 60898 — that's the figure for repeated fault clearing without replacing the breaker.

Ambient operating range -25 to 60 °C, storage -40 to 70 °C; tropicalisation class 2 per IEC 60068-1 handles 95 % RH at 55 °C.

MPN