Schneider Electric C60H4P16AB — 2-Pole MCB (DIN Rail)

Schneider C60H4P16AB MCB, B Curve 16 A 4P, 10 kA

MPNC60H4P16AB
Obsolete

Schneider Electric C60H4P16AB, Multi9 C60H series, miniature circuit breaker, 4-pole, B-curve, 16 A, 10 kA Icn at 230/400 V AC, 72 x 81 x 73 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P16AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P16AB — Electrical
ParameterValue
Rated current [In]16 A at 30 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C60H4P16AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P16AB — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torquePower circuit: 2 N.m upside 2 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P16AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P16AB — Approvals
ParameterValue
Standards / complianceIEC 60947-2 EN 60898

Product details

Integrator's note on the C60H4P16AB

The Schneider Electric C60H4P16AB is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated 16 A with a B-curve trip characteristic (3 to 5 x In magnetic trip). It carries a 10 kA Icn breaking capacity at 230/400 V AC per EN 60898, and higher Icu ratings per IEC 60947-2 — 15 kA at 400–415 V AC, 30 kA at 230–240 V AC. The dual standard means it qualifies for both residential distribution boards (EN 60898) and industrial panel applications (IEC 60947-2), so you can spec it into a commercial MCC or a branch panel without re-certifying the assembly. The 72 mm width (8 x 9 mm pitches) and 73 mm depth fit standard enclosure cutouts — no odd footprint to accommodate.

Do not use it for motor starting; that calls for a C or D curve. The 10 kA Icn at 230/400 V AC is the rated short-circuit capacity under EN 60898; the higher Icu values under IEC 60947-2 (up to 50 kA at 250 V DC for the 4P configuration) give you headroom for industrial fault levels. The Ics (service breaking capacity) is 7.5 kA at 230/400 V AC per EN 60898 — meaning after clearing a fault at that level, the breaker is still usable, not wrecked. Rated operational voltage spans 12–440 V AC 50/60 Hz, and the insulation voltage is 500 V AC. The 4-pole version also carries DC ratings: 25 kA Icu at 125 V DC (2P in series) and 40 kA at 125 V DC (3P in series). That DC capability is useful for battery-backed buswork or UPS distribution panels.

Deployment context

The 4-pole version handles three-phase plus neutral, or four-phase distribution in DC applications. Ambient operating range is -25 to 60 °C, with 95% humidity tolerance at 55 °C and tropicalisation class 2 per IEC 60068-1 — fine for unventilated enclosures in warm climates.

Frequently asked questions

How do I get pricing and availability for C60H4P16AB?

We source the C60H4P16AB through independent distribution and quote it to order against an RFQ. Submit a request for current pricing and availability — both are confirmed at quote time.

What is the breaking capacity of the C60H4P16AB?

The C60H4P16AB carries a 10 kA Icn at 230/400 V AC per EN 60898, and higher Icu ratings per IEC 60947-2: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and up to 50 kA at 250 V DC for the 4-pole configuration.

What does the B-curve mean on this breaker?

The B-curve trips magnetically at 3 to 5 times the rated current (48–80 A for this 16 A unit). It is designed for resistive loads and general-purpose circuits with low inrush — lighting, small heaters, control transformers — not for motor starting.

MPN
C60H4P16AB