Skip to main content
Schneider Electric C60H4P32AC — 2-Pole MCB (DIN Rail)

Schneider C60H4P32AC MCB, C-Curve 32A 4P, 10kA

MPNC60H4P32AC
Obsolete

Schneider Electric Multi9 C60H, C60H4P32AC, miniature circuit breaker, 4-pole, C-curve, 32 A rated current, 10 kA breaking capacity per EN 60898, thermal-magnetic trip unit, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P32AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P32AC — Electrical
ParameterValue
Rated current [In]32 A at 30 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)DC AC
Network frequency50/60 Hz
C60H4P32AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P32AC — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P32AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P32AC — Approvals
ParameterValue
Standards / complianceEN 60898 IEC 60947-2

Product details

The C60H4P32AC is a 4-pole miniature circuit breaker from Schneider Electric's Multi9 C60 range, rated 32 A at 30 °C with a C-curve magnetic trip (5 to 10 x In). The 10 kA Icn at 230/400 V AC per EN 60898 is the rated short-circuit capacity for the breaker under standard conditions; the higher Icu values (up to 30 kA at 230–240 V AC per IEC 60947-2) cover industrial fault levels. For a 4-pole breaker, the 32 A rating and C-curve suit sub-distribution boards where the downstream load includes small motors, lighting, and socket outlets. The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit response. The magnetic threshold at 5–10 x In means the breaker holds through transformer inrush and motor starting current without nuisance tripping, but clears fast on a hard fault.

The toggle control provides local ON/OFF indication and a contact position indicator confirms the state of the moving contacts for isolation verification. The tropicalisation treatment (class 2 per IEC 60068-1) and 95 % relative humidity rating at 55 °C make it suitable for unconditioned electrical rooms and outdoor-rated enclosures in humid climates.

Compliance documentation includes EN 60898 (household and similar installations) and IEC 60947-2 (industrial) standards. The limitation class 3 per IEC 60947-2 indicates energy-limiting performance that reduces let-through energy on faults.

Frequently asked questions

What is C60H4P32AC's listed depth (73 mm) on this component line?

The depth is 73 mm, with a width of 72 mm (8 x 9 mm pitches) and height of 81 mm. These dimensions fit standard 100 mm deep enclosures on a 35 mm DIN rail.

What compliance documentation does this brand provide for C60H4P32AC (RoHS, REACH, UL, IEC)?

The breaker is certified to EN 60898 and IEC 60947-2. It is suitable for isolation per IEC 60947-2, with a rated insulation voltage of 500 V AC. The evidence does not list RoHS, REACH, or UL specifically, but the IEC standards cover the core safety and performance requirements for distribution circuit breakers.

Who supplies C60H4P32AC and how is it quoted for volume purchases?

The C60H4P32AC is sourced to order against an RFQ through independent distribution channels. Volume pricing and lead time are confirmed at quote time — submit an RFQ for current availability and pricing.

MPN
C60H4P32AC