Skip to main content
Schneider Electric C60H4P40AC — 2-Pole MCB (DIN Rail)

Schneider Electric C60H4P40AC MCB, 40 A, 4P, C-Curve, 10 kA

MPNC60H4P40AC
Obsolete

Schneider Electric Multi9 C60H miniature circuit breaker, C60H4P40AC, 40 A rated current, 4-pole, C-curve, 10 kA Icn breaking capacity at 230/400 V AC, thermal-magnetic trip unit, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P40AC — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P40AC — Electrical
ParameterValue
Rated current [In]40 A at 30 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C60H4P40AC — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P40AC — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P40AC — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P40AC — Approvals
ParameterValue
Standards / complianceIEC 60947-2 EN 60898

Product details

Miniature circuit-breaker, 40 A, 4-pole, C-curve — Schneider Electric C60H4P40AC

The Schneider Electric C60H4P40AC is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated at 40 A with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). The thermal-magnetic trip unit provides overcurrent and short-circuit protection, with a breaking capacity of 10 kA Icn at 230/400 V AC per EN 60898, and higher Icu ratings per IEC 60947-2 (up to 30 kA at 230–240 V AC).

The C60H4P40AC carries a rated breaking capacity (Icn) of 10 kA at 230/400 V AC per EN 60898, which covers most commercial and light industrial panelboard applications. For higher fault-current scenarios, the ultimate breaking capacity (Icu) per IEC 60947-2 reaches 30 kA at 230–240 V AC and 15 kA at 400–415 V AC. The service breaking capacity (Ics) is 7.5 kA at 230/400 V AC per EN 60898, and 15 kA at 230–240 V AC per IEC 60947-2. These ratings allow the breaker to be coordinated downstream of a higher-rated upstream device, maintaining selectivity for branch circuits.

The breaker snaps onto a 35 mm symmetrical DIN rail (EN 60715) and occupies 8 modules of 9 mm pitch, for a total width of 72 mm. The depth of 73 mm and height of 81 mm fit standard distribution enclosures.

Frequently asked questions

What is the breaking capacity of C60H4P40AC?

The rated breaking capacity (Icn) is 10 kA at 230/400 V AC per EN 60898. Per IEC 60947-2, the ultimate breaking capacity (Icu) is 30 kA at 230–240 V AC and 15 kA at 400–415 V AC.

What is the C60H4P40AC's rated current and curve?

It is rated at 40 A with a C-curve trip characteristic, meaning magnetic tripping occurs between 5 and 10 times the rated current.

Where can I buy C60H4P40AC?

The C60H4P40AC is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation.

MPN
C60H4P40AC