Skip to main content
Schneider Electric C60H4P50AB — 2-Pole MCB (DIN Rail)

Schneider Electric C60H4P50AB C60H MCB, 50A 4P B-curve, 10kA

MPNC60H4P50AB
Obsolete

Schneider Electric Multi9 C60H series, C60H4P50AB, 4-pole miniature circuit breaker, 50 A rated current, B-curve, 10 kA breaking capacity per EN 60898.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P50AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P50AB — Electrical
ParameterValue
Rated current [In]50 A at 30 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C60H4P50AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P50AB — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P50AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P50AB — Approvals
ParameterValue
Standards / complianceEN 60898 IEC 60947-2

Product details

The Schneider Electric C60H4P50AB is a 4-pole miniature circuit breaker from the Multi9 C60H range, rated at 50 A with a B-curve trip characteristic.

But under IEC 60947-2, the ultimate breaking capacity (Icu) climbs: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and even 50 kA at 250 V DC for the 4-pole configuration. That means the same device can handle a much tougher fault on a 240 V panel or a DC bus than its EN 60898 label suggests — useful if you're spec'ing for a mixed AC/DC installation and want one part number across both.

Fixed mounting on a 35 mm DIN rail, 4-pole wide at 72 mm (8 x 9 mm pitches).

Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, and 95 % relative humidity at 55 °C. Complies with both EN 60898 (household-type MCB standard) and IEC 60947-2 (industrial breaker standard), so it's accepted across residential, commercial, and light industrial panels.

Frequently asked questions

What is the breaking capacity of the C60H4P50AB?

The C60H4P50AB has a 10 kA Icn at 230/400 V AC per EN 60898, and up to 30 kA Icu at 230–240 V AC per IEC 60947-2. For DC applications, it achieves 50 kA Icu at 250 V DC in 4-pole configuration.

Where can I buy the C60H4P50AB?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does the C60H4P50AB comply with?

It complies with EN 60898 and IEC 60947-2, covering both household-type and industrial breaker applications.

Does the C60H4P50AB fit on a standard DIN rail?

Yes, it mounts on a 35 mm symmetrical DIN rail and occupies 72 mm (4 modules) of panel width.

MPN
C60H4P50AB